Walker Industrial: Home > Manufacturers > P - S > SSAC > Timers & Flashers > Liquid Level Controls & Alternating Relays > LLC2 Series

LLC2 Series
Sort By:
1
LLC24A2AN - SSAC LLC24A2AN - SSAC Liquid Level Drain Dual 120VAC Relay Adjustable Open Board

Liquid Level Drain Dual 120VAC Relay Adjustable Open Board (SSAC LLC24A2AN)

Usually Ships in 3 to 5 Days
Price: $82.98
LLC24A2F50N - SSAC LLC24A2F50N - SSAC Liquid Level Drain Dual 120VAC Relay FXD 50K Open Board

Liquid Level Drain Dual 120VAC Relay FXD 50K Open Board (SSAC LLC24A2F50N)

Usually Ships in 3 to 5 Days
Price: $82.98
LLC24B1AC - SSAC LLC24B1AC - SSAC Liquid Level Fill Dual 120VAC Relay Adjustable Open Board

Liquid Level Fill Dual 120VAC Relay Adjustable Open Board (SSAC LLC24B1AC)

Usually Ships in 3 to 5 Days
Price: $79.15
LLC24B2F50N - SSAC LLC24B2F50N - SSAC Liquid Level Fill Dual 120VAC Relay FXD 50K Open Board

Liquid Level Fill Dual 120VAC Relay FXD 50K Open Board (SSAC LLC24B2F50N)

Usually Ships in 3 to 5 Days
Price: $82.98
LLC26A1F25C - SSAC LLC26A1F25C - SSAC Liquid Level Drain Dual 230VAC Relay FXD 25K Open Board

Liquid Level Drain Dual 230VAC Relay FXD 25K Open Board (SSAC LLC26A1F25C)

Usually Ships in 3 to 5 Days
Price: $79.15
   
 
1
LLC2 Series

The LLC2 Series is a dual-probe conductive liquid level control designed for OEM equipment and commercial appliance applications. Models are available for fill or drain operation. Transformer isolated 12VAC is provided at the probes to prevent electrolysis. A trickle current of less than 1mA determines the presence or absence of liquid between the probes and common. On adjustable units, the sensitivity adjustment allows accurate level sensing while ignoring foaming agents and floating debris. The LLC2 Series printed circuit board is conformal coated to resist moisture and corrosion.

Operation
Drain (Pump-Down Mode): When the liquid level rises and touches the high probe, the output relay energizes and remains energized until the liquid level falls below the low probe. The output relay then de-energizes and remains de-energized until the liquid again touches the high probe.

Fill (Pump-Up Mode): When the liquid level falls below the low probe, the output relay energizes and remains energized until the liquid level rises and touches the high probe. The output relay then de-energizes and remains de-energized until the liquid level again falls below the low probe.

Features:

  • Dual probe level control for conductive liquids
  • Isolated AC voltage on the probes
  • Adjustable or fixed sensing up to 100K?
  • Terminal block or quick connect terminals
  • Fill or drain operation available
  • 24, 120, or 230VAC models are available
  • Isolated, 10A, SPDT output contacts Approvals:

Auxiliary Products:

  • Quick connect to screw adaptor: P/N: P1015-18
  • Electrode: P/N: PHST-38QTN
  • Threaded probe (24"): P/N: LLP-24
  • Female quick connect:
    • P/N: P1015-13 (AWG 10/12)
    • P/N: P1015-64 (AWG 14/16)
    • P/N: P1015-14 (AWG 18/22)